■ Precautions for using the illuminance and motion sensors
To integrate sensors with this system, you will need to set up a sensor group that combines the lighting group and the sensors.
Up to one illuminance sensor and up to ten motion sensors can be registered in one group.

It is not possible to control the same lighting group with multiple sensors (illuminance sensor + motion sensor).
Because the command signals from multiple sensors cannot be prioritized, response delays will occur, leading to malfunctions.

It is not possible to configure multiple functions, such as sensors or schedules, for the same lighting group.